Omron 3G3RX-V1 Series

3G3RX-V1

High-function General-purpose Inverters

 3G3RX-V1

High performance to match your application

Free to program

3G3RX-V1 Features 2

Drive Programming enables you to make your own programs to suit your machine, e.g. for an unwinding application. Up to 1000 lines of code and 5 tasks running in parallel in 2 programming modes. 
(CX-Drive version 2.72 or higher is required.)

Positioning functionality

3G3RX-V1 Features 3

Simple positioning is handled by the inverter itself without the need for an external motion controller. Functions include pulse trace position control mode, homing and position teaching.

Network Integration

3G3RX-V1 Features 4

Standard industrial networks, such as EtherCAT, CompoNet or DeviceNet as options. High-speed EtherCAT provides solutions for the entire system from input to output with Sysmac Series. Built-in RS-485 Modbus communications.

Vector Control

3G3RX-V1 Features 5

In addition to V/f control, the following control methods are included. This enables a 200% starting torque at 0.3 Hz. 
-Sensorless vector control 
-Sensorless vector control in 0-Hz domain 
-Vector control with a PG

Space and cost saving

3G3RX-V1 Features 6

The RX-V1 has built-in radio noise filter/EMC filter* that saves on costs and space compared with the standard external filter solution. 
* Selectable

RX series V1 type Inverter Models

 

Rated voltage Enclosure ratings Max. applicable motor capacity Model
CT: Heavy load VT: Light load
3-phase 200 VAC IP20 0.4 kW 0.75 kW 3G3RX-A2004-V1
0.75 kW 1.5 kW 3G3RX-A2007-V1
1.5 kW 2.2 kW 3G3RX-A2015-V1
2.2 kW 3.7 kW 3G3RX-A2022-V1
3.7 kW 5.5 kW 3G3RX-A2037-V1
5.5 kW 7.5 kW 3G3RX-A2055-V1
7.5 kW 11 kW 3G3RX-A2075-V1
11 kW 15 kW 3G3RX-A2110-V1
15 kW 18.5 kW 3G3RX-A2150-V1
18.5 kW 22 kW 3G3RX-A2185-V1
22 kW 30 kW 3G3RX-A2220-V1
30 kW 37 kW 3G3RX-A2300-V1
37 kW 45 kW 3G3RX-A2370-V1
45 kW 55 kW 3G3RX-A2450-V1
55 kW 75 kW 3G3RX-A2550-V1
3-phase 400 VAC 0.4 kW 0.75 kW 3G3RX-A4004-V1
0.75 kW 1.5 kW 3G3RX-A4007-V1
1.5 kW 2.2 kW 3G3RX-A4015-V1
2.2 kW 3.7 kW 3G3RX-A4022-V1
3.7 kW 5.5 kW 3G3RX-A4037-V1
5.5 kW 7.5 kW 3G3RX-A4055-V1
7.5 kW 11 kW 3G3RX-A4075-V1
11 kW 15 kW 3G3RX-A4110-V1
15 kW 18.5 kW 3G3RX-A4150-V1
18.5 kW 22 kW 3G3RX-A4185-V1
22 kW 30 kW 3G3RX-A4220-V1
30 kW 37 kW 3G3RX-A4300-V1
37 kW 45 kW 3G3RX-A4370-V1
45 kW 55 kW 3G3RX-A4450-V1
55 kW 75 kW 3G3RX-A4550-V1
IP00 75 kW 90 kW 3G3RX-B4750-V1
90 kW 110 kW 3G3RX-B4900-V1
110 kW 132 kW 3G3RX-B411K-V1
132 kW 160 kW 3G3RX-B413K-V1

 

Performance Specifications

Inverter 3G3RX-V1

CT: Heavy load rating VT: Light load rating

3-phase 200-V Class

 

3-phase 200-V class
Model name (3G3RX-) A2004- 
V1
A2007- 
V1
A2015- 
V1
A2022- 
V1
A2037- 
V1
A2055- 
V1
A2075- 
V1
A2110- 
V1
Maximum 
applicable motor 
capacity (kW)
CT 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11
VT 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated 
output 
capacity 
(kVA)
200V CT 1.0 1.7 2.5 3.6 5.7 8.3 11.0 15.9
VT 1.2 2.1 3.2 4.1 6.7 10.3 15.2 20.0
240V CT 1.2 2.0 3.1 4.3 6.8 9.9 13.3 19.1
VT 1.5 2.6 3.9 4.9 8.1 12.4 18.2 24.1
Rated input voltage 3-phase 200 V -15% to 240 V +10%, 50/60 Hz ± 5%
Rated input 
current (A)
CT 3.3 5.5 8.3 12 18 26 35 51
VT 3.9 7.2 10.8 13.9 23 37 48 64
Rated output voltage 3-phase 200 to 240 V (Cannot exceed that of incoming voltage)
Rated output 
current (A)
CT 3.0 5.0 7.5 10.5 16.5 24 32 46
VT 3.7 6.3 9.4 12 19.6 30 44 58
EMC Noise Filter Built-in (EMC Directive EN61800-3 Category C3)
Weight (kg) 3.5 3.5 3.5 3.5 3.5 6 6 6
Braking 
Resistor 
circuit
Regenerative 
braking
Built-in Braking Resistor circuit (separate Discharge Resistor)
Min. 
connectable 
resistance 
(Ω)
50 50 35 35 35 16 10 10
Maximum 
leakage 
current 
(mA)
EMC filter 
enabled
2.5 48
EMC filter 
disabled
0.1

 

 

3-phase 200-V class
Model name (3G3RX-) A2150-V1 A2185-V1 A2220-V1 A2300-V1 A2370-V1 A2450-V1 A2550-V1
Maximum 
applicable motor 
capacity (kW)
CT 15 18.5 22 30 37 45 55
VT 18.5 22 30 37 45 55 75
Rated 
output 
capacity 
(kVA)
200V CT 22.1 26.3 32.9 41.9 50.2 63.0 76.2
VT 25.2 29.4 39.1 48.4 58.5 72.7 93.5
240V CT 26.6 31.5 39.4 50.2 60.2 75.6 91.4
VT 30.3 35.5 46.9 58.1 70.2 87.2 112.2
Rated input voltage 3-phase 200 V -15% to 240 V +10%, 50/60 Hz ± 5%
Rated input 
current (A)
CT 70 84 105 133 160 200 242
VT 80 94 120 150 186 240 280
Rated output voltage 3-phase 200 to 240 V (Cannot exceed that of incoming voltage)
Rated output 
current (A)
CT 64 76 95 121 145 182 220
VT 73 85 113 140 169 210 270
EMC Noise Filter Built-in (EMC Directive EN61800-3 Category C3)
Weight (kg) 14 14 14 22 30 30 43
Braking 
Resistor 
circuit
Regenerative 
braking
Built-in Braking Resistor circuit 
(separate Discharge Resistor)
Separate Regenerative Braking Unit
Min. 
connectable 
resistance 
(Ω)
7.5 7.5 5 ---
Maximum 
leakage 
current 
(mA)
EMC filter 
enabled
23
EMC filter 
disabled
0.1

 

3-phase 400-V Class

 

3-phase 400-V class
Model name (3G3RX-) A4004- 
V1
A4007- 
V1
A4015- 
V1
A4022- 
V1
A4037- 
V1
A4055- 
V1
A4075- 
V1
Maximum 
applicable motor 
capacity (kW)
CT 0.4 0.75 1.5 2.2 3.7 5.5 7.5
VT 0.75 1.5 2.2 3.7 5.5 7.5 11
Rated 
output 
capacity 
(kVA)
400V CT 1.0 1.7 2.6 3.6 6.2 9.6 13.1
VT 1.3 2.1 3.3 4.6 7.6 11.0 15.2
480V CT 1.2 2.0 3.1 4.4 7.4 11.6 15.7
VT 1.5 2.5 3.9 5.5 9.2 13.3 18.2
Rated input voltage 3-phase 380 V -15% to 480 V +10%, 50/60 Hz ± 5%
Rated input 
current (A)
CT 1.8 2.8 4.2 5.8 9.8 15 21
VT 2.1 4.3 5.9 8.1 13.3 20 24
Rated output voltage 3-phase 380 to 480 V (Cannot exceed that of incoming voltage)
Rated output 
current (A)
CT 1.5 2.5 3.8 5.3 9.0 14 19
VT 1.9 3.1 4.8 6.7 11.1 16 22
EMC Noise Filter Built-in (EMC Directive EN61800-3 Category C3)
Weight (kg) 3.5 3.5 3.5 3.5 3.5 6 6
Braking 
Resistor 
circuit
Regenerative 
braking
Built-in Braking Resistor circuit (separate Discharge Resistor)
Min. 
connectable 
resistance 
(Ω)
100 100 100 100 70 70 35
Maximum 
leakage 
current 
(mA)
EMC filter 
enabled
5 95
EMC filter 
disabled
0.2

 

 

3-phase 400-V class
Model name (3G3RX-) A4110-V1 A4150-V1 A4185-V1 A4220-V1 A4300-V1 A4370-V1
Maximum 
applicable motor 
capacity (kW)
CT 11 15 18.5 22 30 37
VT 15 18.5 22 30 37 45
Rated 
output 
capacity 
(kVA)
400V CT 17.3 22.1 26.3 33.2 40.1 51.9
VT 20.0 25.6 29.7 39.4 48.4 58.8
480V CT 20.7 26.6 31.5 39.9 48.2 62.3
VT 24.1 30.7 35.7 47.3 58.1 70.6
Rated input voltage 3-phase 380 V -15% to 480 V +10%, 50/60 Hz ± 5%
Rated input 
current (A)
CT 28 35 42 53 64 83
VT 32 41 47 63 77 94
Rated output voltage 3-phase 380 to 480 V (Cannot exceed that of 
incoming voltage)
3-phase 380 to 480 V 
(according to the input voltage)
Rated output 
current (A)
CT 25 32 38 48 58 75
VT 29 37 43 57 70 85
EMC Noise Filter Built-in (EMC Directive EN61800-3 Category C3)
Weight (kg) 6 14 14 14 22 30
Braking 
Resistor 
circuit
Regenerative 
braking
Built-in Braking Resistor circuit (separate Discharge 
Resistor)
Separate Regenerative Braking 
Unit
Min. connectable 
resistance (Ω)
35 24 24 20 ---
Maximum 
leakage 
current 
(mA)
EMC filter 
enabled
95 56
EMC filter 
disabled
0.2

 

 

3-phase 400-V class
Model name (3G3RX-) A4450-V1 A4550-V1 B4750-V1 B4900-V1 B411K-V1 B413K-V1
Maximum applicable 
motor capacity (kW)
CT 45 55 75 90 110 132
VT 55 75 90 110 132 160
Rated output 
capacity (kVA)
400V CT 63.0 77.5 103.2 121.9 150.3 180.1
VT 72.7 93.5 110.8 135 159.3 200.9
480V CT 75.6 93.1 123.8 146.3 180.4 216.1
VT 87.2 112.2 133 162.1 191.2 241.1
Rated input voltage 3-phase 380 V -15% to 480 V +10%, 50/60 Hz ± 5%
Rated input current 
(A)
CT 100 121 164 194 239 286
VT 116 149 176 199 253 300
Rated output voltage 3-phase 380 to 480 V (according to the input voltage)
Rated output current 
(A)
CT 91 112 149 176 217 260
VT 105 135 160 195 230 290
EMC Noise Filter Built-in (EMC Directive EN61800-3 Category C3)
Weight (kg) 30 30 55 55 70 70
Braking 
Resistor 
circuit
Regenerative 
braking
Separate Regenerative Braking Unit
Min. connectable 
resistance (Ω)
---
Maximum 
leakage 
current (mA)
EMC filter 
enabled
56 0.2 (No enabled/disabled setting available)
EMC filter 
disabled
0.2

 

Function Specifications

Inverter 3G3RX-V1

 

Function name Specifications
Enclosure ratings IP20 (0.4 to 55 kW) 
IP00 (75 to 132 kW)
Control method Phase-to-phase sinusoidal modulation PWM
Output frequency range 0.1 to 400 Hz
Frequency precision Digital command: ±0.01% of the maximum frequency, Analog command: ±0.2% 
of the maximum frequency (25±10°C)
Frequency resolution Digital setting: 0.01 Hz 
Analog setting: maximum frequency/4000 
(Terminal FV: 12 bits/0 to +10 V), (Terminal FE: 12 bits/-10 to 10 V), (Terminal 
FI: 12 bits/0 to 20 mA)
Voltage/Frequency 
characteristics
Heavy load rating (CT): V/f characteristics (constant torque, reduced torque, 
free V/f setting), sensorless vector control, 0-Hz sensorless vector control, 
sensor vector control 
Light load rating (VT): V/f characteristics (constant torque, reduced torque, 
free V/f setting), sensorless vector control
Overload current rating Heavy load rating (CT): 150%/60 s, 200%/3 s (180%/3 s for 75 kW or more) 
Light load rating (VT): 120%/60 s, 150%/5 s
Instantaneous overcurrent 
protection
200% of the value of heavy load rating (CT)
Acceleration/Deceleration time 0.01 to 3600 s (linear/curve selection)
Speed fluctuation Heavy load rating (CT): ± 0.5% *1, *2 
Light load rating (VT): ± 0.5% *1
Carrier frequency adjustment 
range
(For 0.4 to 55kW) 
Heavy load rating (CT): 0.5 to15 kHz 
Light load rating (VT): 0.5 to12 kHz
(For 75 to 132kW) 
Heavy load rating (CT): 0.5 to 10 kHz 
Light load rating (VT): 0.5 to 8 kHz
Starting 
torque
Sensor less vector 
control
(For 0.4 to 55kW) 
Heavy load rating (CT): 200%/0.3 Hz *1
Light load rating (VT): 150%/0.5 Hz *1
(For 75 to 132kW) 
Heavy load rating (CT): 180%/0.3 Hz *1
Light load rating (VT): 120%/0.5 Hz *1
0-Hz sensorless 
vector control
(For 0.4 to 55kW) 
Heavy load rating (CT): 150%/Torque at
0 Hz *3 
Light load rating (VT): No function 
available
(For 75 to132kW) 
Heavy load rating (CT): 130%/Torque at
0 Hz *3 
Light load rating (VT): No function 
available
External DC injection braking Operates when the starting frequency is lower than that in deceleration via the 
STOP command, when the frequency reference is lower than the operation 
frequency, or via an external input (braking power, time, and frequency are 
variable)
Protective functions Overcurrent protection, Overvoltage protection, Undervoltage protection, 
Electronic thermal protection, Temperature error protection, Momentary power 
interruption/Power interruption protection, Input phase loss protection, Braking 
resistor overload protection, Ground-fault current detection at power-on, USP 
error, External trip, Emergency shutoff trip, CT error, Communication error, 
Option error, etc.
Input 
signal
Frequency 
settings
Standard
Digital 
Operator
Setting via 3146_sp_3_1keys
External 
signal *4
0 to 10 VDC, -10 to 10 VDC (Input impedance: 10 kΩ), 4 to 20 mA (Input 
impedance: 100 Ω)
External 
port
Setting through RS-485 communications
Forward or 
Reverse 
operation/ 
Stop
Standard
Digital 
Operator
RUN/STOP (Forward/reverse switched via parameter settings)
External 
signal
Forward/Stop (Reverse/Stop available at the time of multi-functional input 
terminal allocation), 3-wire input available (at the time of control circuit 
terminal block allocation)
External 
port
Setting through RS-485 communications
Multi-function input 
*5
8 terminals, NO/NC switchable, sink/source logic switchable 
Heavy load (CT): 8 functions can be selected from among 72 
Light load (VT): 8 functions can be selected from among 57
Thermistor input 
terminal
1 terminal (Positive/Negative temperature coefficient of resistance element 
switchable)
Output 
signal
Multi-function output 
*5
5 open collector output terminals: NO/NC switchable, sink/source logic 
switchable 
1 relay (SPDT contact) output terminal: NO/NC switchable 
Heavy load (CT): 6 functions can be selected from among 55 
Light load (VT): 6 functions can be selected from among 51
Multi-function monitor 
output terminal
Analog voltage output (0 to 10 V) *6 , Analog current output (0 to 20 mA) *6, 
Pulse train output (maximum frequency 3.6 kHz)
Display monitor Output frequency, Output current, Output torque, Frequency conversion value, 
Trip record, I/O terminal status, Electric power, etc.
Other functions Heavy load rating (CT) 
V/f free setting (7), Upper/lower frequency limit, Frequency jump, Curve 
acceleration/deceleration, Manual torque boost level/break, Energy-saving 
operation, Analog meter adjustment, Starting frequency, Carrier frequency 
adjustment, Electronic thermal function (free setting available), External start/ 
end (frequency/rate), Analog input selection, Trip retry, Restart during 
momentary power interruption, Various signal outputs, Reduced voltage startup, 
Overload limit, Initialization value setting, Automatic deceleration at power-off, 
AVR function, Automatic acceleration/deceleration, Auto tuning (Online/ 
Offline)
Light load rating (VT) 
V/f free setting (7), Upper/lower frequency limit, Frequency jump, Curve 
acceleration/deceleration, Manual torque boost level/break, Energy-saving 
operation, Analog meter adjustment, Starting frequency, Carrier frequency 
adjustment, Electronic thermal function (free setting available), External start/ 
end (frequency/rate), Analog input selection, Trip retry, Restart during 
momentary power interruption, Various signal outputs, Reduced voltage startup, 
Overload limit, Initialization value setting, Automatic deceleration at power-off, 
AVR function, Auto tuning (Online/Offline)
Operating 
envi- 
ronment
Ambient operating 
temperature
Heavy load rating (CT): -10 to 50°C 
Light load rating (VT): -10 to 40°C
Ambient storage 
temperature
-20 to 65°C
Ambient operating 
humidity
20% to 90% (with no condensation)
Vibration resistance 
*7
5.9m/s2 (0.6G), 10 to 55Hz/0.4 to 22 kW 
2.94m/s2 (0.3G), 10 to 55Hz/30 to 132 kW
Application 
environment
At a maximum altitude of 1,000 m (without corrosive gases or dust) *8
Options PG Board Sensor vector control 3G3AX-PG01
EtherCAT 
Communication Unit
3G3AX-RX-ECT
CompoNet™ 
Communication Unit
3G3AX-RX-CRT-E
DeviceNet™ 
Communication Unit
3G3AX-RX-DRT-E
Other options Braking Resistor, AC reactor, DC reactor, Digital Operator, Digital Operator 
cables, Noise filter, Regenerative braking unit, etc.
Interna- 
tional 
standard
EC 
Directive
EMC 
Directive
EN61800-3: 2004
Low 
Voltage 
Directive
EN61800-5-1: 2003
UL/cUL UL508C