Skip to content
PHOENIX TECHNOLOGIES, BANGALORE | 📞 Call us on 080 42100546, Mob : 7760459320 | Email : info@phoenixtechnologies.org
PHOENIX TECHNOLOGIES, BANGALORE | 📞 Call us on 080 42100546, Mob : 7760459320 | Email : info@phoenixtechnologies.org

Omron 3G3MX2-V1 Series

3G3MX2-V1

3G3MX2-V1

Amazing in Control

High starting torque and torque control capability in open loop mode give you full control of your machine dynamics and performance. Options for all of the major open network systems.

Torque master

3G3MX2-V1 Features 2

The MX2-V1 delivers 200% starting torque near stand-still (0.5 Hz) and can operate in torque control in open loop mode. This allows the MX2-V1 to be used in applications where closed loop AC vector drives were previously used.

Easy network integration

3G3MX2-V1 Features 3

Standard industrial networks, such as EtherCAT, CompoNet or DeviceNet as options. High-speed EtherCAT provides solutions for the entire system from input to output with Sysmac Series.

Easy communications setting

3G3MX2-V1 Features 4

Built-in RS-485 Modbus communications. OMRON Function Blocks are available for the CP H/L and CJ-series PLCs. Those control the MX2-V1 via Modbus communications easily.

Safety in Control

Safety is embedded in the MX2-V1, according to ISO 13849-1, Cat. 3, with two safety inputs and an External Device Monitoring (EDM) output. 
No external contactors on the motor side are required, meaning simpler wiring for the user.

Safety embedded; ISO 13849-1, Cat. 3

3G3MX2-V1 Features 6

Dual contactors at the output of the inverter are no longer required. 
Direct connection to a safety controller ensures compliance to ISO 13849-1, Cat. 3.

MOTOR CONTROL Permanent magnet motors

3G3MX2-V1 Features 7

The PM motor conforming to high-efficiency regulations can be controlled. The PM motor promotes further energy saving and achieves earth-friendly machine control.

Position and run!

The MX2-V1 is a drive and position controller in one, ideal for modular machines where moderate positional accuracy is required. Speed synchronisation is also possible, with no additional programming required.

Speed synchronisation

3G3MX2-V1 Features 9

With no external hardware required, and via standard parameter settings, speed synchronisation can be achieved. The MX2-V1 will act as a speed follower to an external pulse generator/encoder signal up to 32 KHz.

Positioning functionality

3G3MX2-V1 Features 10

Specially developed application functionality enables the MX2-V1 to solve simple positioning tasks without the need for an external controller. Up to 8 positions, plus home, can be selected by the user, and furthermore, the MX2-V1 can be switched between speed and position mode.

Program and play!

The MX2-V1 gives you the power to create smart solutions using PLC functionality, as standard. Via an intuitive flow chart programming tool, you can create programs with up to 1000 lines of code and with 5 tasks running in parallel.

Free to program

3G3MX2-V1 Features 12

 

• Intuitive and user friendly flow chart programming 
• Integrated in CX-Drive 
• Up to 1000 lines in a program 
• 5 tasks can run in parallel 
   (CX-Drive version 2.80 or higher is required.)

Interpreting Model Numbers

3G3MX2-V1 Lineup 1

3G3MX2 Inverter Models

 

Note: Inverters with model numbers ending in "-V1" are designed to be used in areas other than China and Europe. 
           Refer to the above "Interpreting Model Numbers" for the model numbers for China and Europe.

 

 

Rated voltage Enclosure ratings Max. applicable motor capacity Model
CT: Heavy load VT: Light load
3-phase 200 VAC IP20 0.1 kW 0.2 kW 3G3MX2-A2001-V1
0.2 kW 0.4 kW 3G3MX2-A2002-V1
0.4 kW 0.75 kW 3G3MX2-A2004-V1
0.75 kW 1.1 kW 3G3MX2-A2007-V1
1.5 kW 2.2 kW 3G3MX2-A2015-V1
2.2 kW 3.0 kW 3G3MX2-A2022-V1
3.7 kW 5.5 kW 3G3MX2-A2037-V1
5.5 kW 7.5 kW 3G3MX2-A2055-V1
7.5 kW 11 kW 3G3MX2-A2075-V1
11 kW 15 kW 3G3MX2-A2110-V1
15 kW 18.5 kW 3G3MX2-A2150-V1
3-phase 400 VAC IP20 0.4 kW 0.75 kW 3G3MX2-A4004-V1
0.75 kW 1.5 kW 3G3MX2-A4007-V1
1.5 kW 2.2 kW 3G3MX2-A4015-V1
2.2 kW 3.0 kW 3G3MX2-A4022-V1
3.0 kW 4.0 kW 3G3MX2-A4030-V1
4.0 kW 5.5 kW 3G3MX2-A4040-V1
5.5 kW 7.5 kW 3G3MX2-A4055-V1
7.5 kW 11 kW 3G3MX2-A4075-V1
11 kW 15 kW 3G3MX2-A4110-V1
15 kW 18.5 kW 3G3MX2-A4150-V1
1-phase 200 VAC IP20 0.1 kW 0.2 kW 3G3MX2-AB001-V1
0.2 kW 0.4 kW 3G3MX2-AB002-V1
0.4 kW 0.55 kW 3G3MX2-AB004-V1
0.75 kW 1.1 kW 3G3MX2-AB007-V1
1.5 kW 2.2 kW 3G3MX2-AB015-V1
2.2 kW 3.0 kW 3G3MX2-AB022-V1

 

Communication Unit

 

Name Model
EtherCAT Communication Unit 3G3AX-MX2-ECT
CompoNet Communication Unit 3G3AX-MX2-CRT-E
DeviceNet Communication Unit 3G3AX-MX2-DRT-E

 

Related Options

 

Name Specifications Model
Regenerative 
Braking Units
3-phase 200 VAC General purpose with Braking resistor 3G3AX-RBU21
High Regeneration purpose with Braking resistor 3G3AX-RBU22
3-phase 400 VAC General purpose with Braking resistor 3G3AX-RBU41
Braking Resistor Compact type Resistor 120 W, 180 Ω 3G3AX-RBA1201
Resistor 120 W, 100 Ω 3G3AX-RBA1202
Resistor 120 W, 5 Ω 3G3AX-RBA1203
Resistor 120 W, 35 Ω 3G3AX-RBA1204
Standard type Resistor 200 W, 180 Ω 3G3AX-RBB2001
Resistor 200 W, 100 Ω 3G3AX-RBB2002
Resistor 300 W, 50 Ω 3G3AX-RBB3001
Resistor 400 W, 35 Ω 3G3AX-RBB4001
Medium capacity type Resistor 400 W, 50 Ω 3G3AX-RBC4001
Resistor 600 W, 35 Ω 3G3AX-RBC6001
Resistor 1200 W, 17 Ω 3G3AX-RBC12001

 

Regenerative Braking Unit and Braking Resistor Combination

 

Inverter Usage 
conditions
Regenerative 
braking unit
Braking resistor Con-
nec- 
tion 
con- 
figu- 
ra- 
tion
Restrictions
Volt- 
age
Max. 
appli- 
cable 
motor
ca- 
pacity
(kW)
Model %ED 
*1 
(%)
Ap- 
proxi- 
mate 
braking
torque 
(% *2)
Model Num-
ber 
of 
units
Model Num-
ber 
of 
units
Allowa- 
ble 
contin- 
uous 
braking
time 
(s)
Min. 
con- 
nect- 
able 
resis- 
tance 
(Ω)
200-V
Class
0.1 3G3MX2- 
A2001-V1
3G3MX2- 
AB001-V1
3.0% 220% Built-in 
Inverter
3G3AX-RBA1201 1 1 20 100
10.0% 220% 3G3AX-RBB2001 1 1 30 100
0.2 3G3MX2- 
A2002-V1
3G3MX2- 
AB002-V1
3.0% 220% Built-in 
Inverter
3G3AX-RBA1201 1 1 20 100
10.0% 220% 3G3AX-RBB2001 1 1 30 100
0.4 3G3MX2- 
A2004-V1
3G3MX2- 
AB004-V1
3.0% 220% Built-in 
Inverter
3G3AX-RBA1201 1 1 20 100
10.0% 220% 3G3AX-RBB2001 1 1 30 100
0.75 3G3MX2- 
A2007-V1
3G3MX2- 
AB007-V1
3.0% 120% Built-in 
Inverter
3G3AX-RBA1201 1 1 20 50
10.0% 120% 3G3AX-RBB2001 1 1 30 50
1.5 3G3MX2- 
A2015-V1
3G3MX2- 
AB015-V1
2.5% 110% Built-in 
Inverter
3G3AX-RBA1202 1 1 12 50
10.0% 215% 3G3AX-RBC4001 1 1 10 50
2.2 3G3MX2- 
A2022-V1
3G3MX2- 
AB022-V1
3.0% 150% Built-in 
Inverter
3G3AX-RBB3001 1 1 30 35
10.0% 150% 3G3AX-RBC4001 1 1 10 35
3.7 3G3MX2- 
A2037-V1
3.0% 125% Built-in 
Inverter
3G3AX-RBB4001 1 1 20 35
10.0% 125% 3G3AX-RBC6001 1 1 10 35
5.5 3G3MX2- 
A2055-V1
3.0% 120% Built-in 
Inverter
3G3AX-RBB3001 2 2 30 20
10.0% 120% 3G3AX-RBC4001 2 2 10 20
7.5 3G3MX2- 
A2075-V1
3.0% 125% Built-in 
Inverter
3G3AX-RBB4001 2 2 20 17
10.0% 125% 3G3AX-RBC6001 2 2 10 17
11 3G3MX2- 
A2110-V1
3.0% 90% Built-in 
Inverter
3G3AX-RBC12001 1 1 10 17
10.0% 90% 3G3AX-RBC12001 1 1 10 17
10.0% 125% 3G3AX-
RBU23 
*3
1 3G3AX-RBC6001 3 14 10 4
15 3G3MX2- 
A2150-V1
3.0% 110% Built-in 
Inverter
3G3AX-RBB3001 5 7 30 10
10.0% 110% 3G3AX-RBC4001 5 7 10 10
400-V
Class
0.4 3G3MX2- 
A4004-V1
3.0% 220% Built-in 
Inverter
3G3AX-RBA1201 2 3 20 180
10.0% 220% 3G3AX-RBB2001 2 3 30 180
0.75 3G3MX2- 
A4007-V1
3.0% 220% Built-in 
Inverter
3G3AX-RBA1201 2 3 20 180
10.0% 220% 3G3AX-RBB2001 2 3 30 180
1.5 3G3MX2- 
A4015-V1
3.0% 120% Built-in 
Inverter
3G3AX-RBA1201 2 3 20 180
10.0% 120% 3G3AX-RBB2001 2 3 30 180
2.2 3G3MX2- 
A4022-V1
2.5% 150% Built-in 
Inverter
3G3AX-RBA1202 2 3 12 100
10.0% 220% 3G3AX-RBC4001 2 3 10 100
3.0 3G3MX2- 
A4030-V1
2.5% 110% Built-in 
Inverter
3G3AX-RBA1202 2 3 12 100
10.0% 215% 3G3AX-RBC4001 2 3 10 100
4.0 3G3MX2- 
A4040-V1
3.0% 165% Built-in 
Inverter
3G3AX-RBB3001 2 3 30 100
10.0% 165% 3G3AX-RBC4001 2 3 10 100
5.5 3G3MX2- 
A4055-V1
3.0% 120% Built-in 
Inverter
3G3AX-RBB3001 2 3 30 70
10.0% 120% 3G3AX-RBC4001 2 3 10 70
7.5 3G3MX2- 
A4075-V1
3.0% 125% Built-in 
Inverter
3G3AX-RBB4001 2 3 20 70
10.0% 125% 3G3AX-RBC6001 2 3 10 70
11 3G3MX2- 
A4110-V1
3.0% 85% Built-in 
Inverter
3G3AX-RBB4001 2 3 20 70
10.0% 85% 3G3AX-RBC6001 2 3 10 70
10.0% 120% 3G3AX-
RBU41 
*3
1 3G3AX-RBC4001 4 15 10 34
15 3G3MX2- 
A4150-V1
3.0% 125% Built-in 
Inverter
3G3AX-RBB4001 4 5 20 35
10.0% 125% 3G3AX-RBC6001 4 5 10 35

 

Performance Specifications

Inverter MX2-series V1 type

3-phase 200 V Class

 

Function name 3-phase 200 V
Model name (3G3MX2-) A2001-V1 A2002-V1 A2004-V1 A2007-V1 A2015-V1 A2022-V1
Applicable 
motor capacity
kW CT 0.1 0.2 0.4 0.75 1.5 2.2
VT 0.2 0.4 0.75 1.1 2.2 3.0
HP CT 1/8 1/4 1/2 1 2 3
VT 1/4 1/2 1 1 1/2 3 4
Rated output 
capacity [kVA]
200 V CT 0.2 0.5 1.0 1.7 2.7 3.8
VT 0.4 0.6 1.2 2.0 3.3 4.1
240 V CT 0.3 0.6 1.2 2.0 3.3 4.5
VT 0.4 0.7 1.4 2.4 3.9 4.9
Rated input voltage 3-phase 200 V - 15% to 240 V + 10%, 50/60 Hz ± 5%
Rated input current [A] CT 1.0 1.6 3.3 6 9 12.7
VT 1.2 1.9 3.9 7.2 10.8 13.9
Rated output voltage 3-phase 200 to 240 V (The output cannot exceed the incoming voltage).
Rated output current [A] CT 1.0 1.6 3.0 5.0 8.0 11.0
VT 1.2 1.9 3.5 6.0 9.6 12.0
Short-time deceleration braking 
torque (%) 
(Discharge Resistor not 
connected)
50 50 50 50 50 20
Braking 
Resistor 
circuit *
Regenerative 
braking
Built-in Braking Resistor circuit (separate Discharge Resistor)
Min. 
connectable 
resistance [Ω]
100 100 100 50 50 35
Weight [kg] 1.0 1.0 1.1 1.2 1.6 1.8
Dimensions (width × height) 
[mm]
68 × 128 108 × 128
Dimensions (depth) [mm] 109 122.5 145.5 170.5

 

 

Function name 3-phase 200 V
Model name (3G3MX2-) A2037-V1 A2055-V1 A2075-V1 A2110-V1 A2150-V1
Applicable 
motor capacity
kW CT 3.7 5.5 7.5 11 15
VT 5.5 7.5 11 15 18.5
HP CT 5 7 1/2 10 15 20
VT 7 1/2 10 15 20 25
Rated output 
capacity [kVA]
200 V CT 6.0 8.6 11.4 16.2 20.7
VT 6.7 10.3 13.8 19.3 23.9
240 V CT 7.2 10.3 13.7 19.5 24.9
VT 8.1 12.4 16.6 23.2 28.6
Rated input voltage 3-phase 200 V - 15% to 240 V + 10%, 50/60 Hz ± 5%
Rated input current [A] CT 20.5 30.8 39.6 57.1 62.6
VT 23.0 37.0 48.0 68.0 72.0
Rated output voltage 3-phase 200 to 240 V (The output cannot exceed the incoming voltage).
Rated output current [A] CT 17.5 25.0 33.0 47.0 60.0
VT 19.6 30.0 40.0 56.0 69.0
Short-time deceleration braking 
torque (%) 
(Discharge Resistor not connected)
20 20 20 10 10
Braking 
Resistor 
circuit *
Regenerative braking Built-in Braking Resistor circuit (separate Discharge Resistor)
Min. connectable resistance [Ω] 35 20 17 17 10
Weight [kg] 2.0 3.3 3.4 5.1 7.4
Dimensions (width × height) [mm] 140 × 128 140 × 260 180 × 296 220 × 350
Dimensions (depth) [mm] 170.5 155 175

 

* The BRD usage is 10%.

3-phase 400 V Class

 

Function name 3-phase 400 V
Model name (3G3MX2-) A4004-V1 A4007-V1 A4015-V1 A4022-V1 A4030-V1
Applicable 
motor capacity
kW CT 0.4 0.75 1.5 2.2 3.0
VT 0.75 1.5 2.2 3.0 4.0
HP CT 1/2 1 2 3 4
VT 1 2 3 4 5
Rated output 
capacity [kVA]
380 V CT 1.1 2.2 3.1 3.6 4.7
VT 1.3 2.6 3.5 4.5 5.7
480 V CT 1.4 2.8 3.9 4.5 5.9
VT 1.7 3.4 4.4 5.7 7.3
Rated input voltage 3-phase 380 V - 15% to 480 V + 10%, 50/60 Hz ± 5%
Rated input current [A] CT 1.8 3.6 5.2 6.5 7.7
VT 2.1 4.3 5.9 8.1 9.4
Rated output voltage 3-phase 380 to 480 V (The output cannot exceed the incoming voltage).
Rated output current [A] CT 1.8 3.4 4.8 5.5 7.2
VT 2.1 4.1 5.4 6.9 8.8
Short-time deceleration braking 
torque (%) 
(Discharge Resistor not connected)
50 50 50 20 20
Braking 
Resistor 
circuit *
Regenerative braking Built-in Braking Resistor circuit (separate Discharge Resistor)
Min. connectable resistance [Ω] 180 180 180 100 100
Weight [kg] 1.5 1.6 1.8 1.9 1.9
Dimensions (width × height) [mm] 108 × 128
Dimensions (depth) [mm] 143.5 170.5

 

 

Function name 3-phase 400 V
Model name (3G3MX2-) A4040-V1 A4055-V1 A4075-V1 A4110-V1 A4150-V1
Applicable 
motor capacity
kW CT 4.0 5.5 7.5 11 15
VT 5.5 7.5 11 15 18.5
HP CT 5 7 1/2 10 15 20
VT 7 1/2 10 15 20 25
Rated output 
capacity [kVA]
380 V CT 6.0 9.7 11.8 15.7 20.4
VT 7.3 11.5 15.1 20.4 25.0
480 V CT 7.6 12.3 14.9 19.9 25.7
VT 9.2 14.5 19.1 25.7 31.5
Rated input voltage 3-phase 380 V - 15% to 480 V + 10%, 50/60 Hz ± 5%
Rated input current [A] CT 11.0 16.9 18.8 29.4 35.9
VT 13.3 20.0 24.0 38.0 44.0
Rated output voltage 3-phase 380 to 480 V (The output cannot exceed the incoming voltage).
Rated output current [A] CT 9.2 14.8 18.0 24.0 31.0
VT 11.1 17.5 23.0 31.0 38.0
Short-time deceleration braking 
torque (%) 
(Discharge Resistor not connected)
20 20 20 10 10
Braking 
Resistor 
circuit *
Regenerative braking Built-in Braking Resistor circuit (separate Discharge Resistor)
Min. connectable resistance [Ω] 100 70 70 70 35
Weight [kg] 2.1 3.5 3.5 4.7 5.2
Dimensions (width × height) [mm] 140 × 128 140 × 260 180 × 296
Dimensions (depth) [mm] 170.5 155 175

 

* The BRD usage is 10%.

1-phase 200 V Class

 

Function name 1-phase 200 V
Model name (3G3MX2-) AB001-V1 AB002-V1 AB004-V1 AB007-V1 AB015-V1 AB022-V1
Applicable 
motor 
capacity
kW CT 0.1 0.2 0.4 0.75 1.5 2.2
VT 0.2 0.4 0.55 1.1 2.2 3.0
HP CT 1/8 1/4 1/2 1 2 3
VT 1/4 1/2 3/4 1 1/2 3 4
Rated 
output 
capacity 
[kVA]
200 V CT 0.2 0.5 1.0 1.7 2.7 3.8
VT 0.4 0.6 1.2 2.0 3.3 4.1
240 V CT 0.3 0.6 1.2 2.0 3.3 4.5
VT 0.4 0.7 1.4 2.4 3.9 4.9
Rated input voltage 1-phase 200 V - 15% to 240 V + 10%, 50/60 Hz ± 5%
Rated input current [A] CT 1.3 3.0 6.3 11.5 16.8 22.0
VT 2.0 3.6 7.3 13.8 20.2 24.0
Rated output voltage 3-phase 200 to 240 V (The output cannot exceed the incoming voltage).
Rated output current [A] CT 1.0 1.6 3.0 5.0 8.0 11.0
VT 1.2 1.9 3.5 6.0 9.6 12.0
Short-time deceleration braking 
torque (%) 
(Discharge Resistor not 
connected)
50 50 50 50 50 20
Braking 
Resistor 
circuit *
Regenerative braking Built-in Braking Resistor circuit (separate Discharge Resistor)
Min. connectable 
resistance [ Ω ]
100 100 100 50 50 35
Weight [kg] 1.0 1.0 1.1 1.6 1.8 1.8
Dimensions (width × height) 
[mm]
68 × 128 108 × 128
Dimensions (depth) [mm] 109 122.5 170.5

 

* The BRD usage is 10%.

Function Specifications

 

Function name Specifications
Enclosure ratings *1 Open type (IP20)
Control Control method Phase-to-phase sinusoidal modulation PWM
Output frequency range
*2
0.10 to 400 Hz (or 580 Hz in the high-frequency mode; restrictions apply)
Frequency precision *3 Digital command: ±0.01% of the max. frequency, Analog command: ±0.2% of 
the max. frequency (25±10 °C)
Frequency setting 
resolution
Digital setting: 0.01 Hz, Analog setting: One-thousandth of the maximum 
frequency
Voltage/Frequency 
characteristics
V/f characteristics (constant/reduced torque) 
Sensorless vector control, V/f control with speed feedback
Overload current rating Heavy load rating (CT): 150%/60 s 
Light load rating (VT): 120%/60 s
Instantaneous 
overcurrent protection
200% of the value of heavy load rating (CT)
Acceleration/ 
Deceleration time
0.01 to 3600 s (linear/curve selection), acceleration/deceleration 2 setting 
vailable
Carrier frequency 
adjustment range
2 to 15 kHz (with derating)
Starting torque 200%/0.5 Hz (sensorless vector control)
External DC injection 
braking
Starts at a frequency lower than that in deceleration via the STOP command, 
at a value set lower than that during operation, or via an external input. (Level 
and time settable).
Protective functions Overcurrent, overvoltage, undervoltage, electronic thermal, temperature 
error, ground fault overcurrent at power-on status, rush current prevention 
circuit, overload limit, incoming overvoltage, external trip, memory error, CPU 
error, USP error, communication error, overvoltage suppression during 
deceleration, protection upon momentary power outage, emergency cutoff, etc.
Input 
signal
Frequency settings Digital Operator 
External analog input signal: 0 to 10 VDC/4 to 20 mA, Modbus communication 
(Modbus-RTU)
RUN/STOP command Digital Operator 
External digital input signal (3-wire input supported), Modbus communication 
(Modbus-RTU)
Multi-function input 7 points (Selectable from 59 functions)
Analog input 2 points (Voltage FV terminal: 10 bits/0 to 10 V, Current FI terminal: 10 bits/4 
to 20 mA)
Pulse input 1 point (RP terminal: 32 kHz max., 5 to 24 VDC)
Output 
signal
Multi-function output 2 points (P1/EDM, P2; selectable from 43 functions)
Relay output 1 point (1c contact: MC, MA, MB; selectable from 43 functions)
Analog output 
(Frequency monitor)
1 point (AM terminal: Voltage 10 bits/0 to 10 V) (Frequency, current selectable)
Pulse output 1 point (MP terminal: 32 kHz max., 0 to 10 V)
Communi-
cations
RS-422 RJ45 connector (for Digital Operator)
RS-485 Control circuit terminal block, Modbus communication (Modbus-RTU)
USB USB1.1, mini-B connector
Drive Programming *4 Calculate, Logic, Control I/O and so on
Other functions AVR function, V/f characteristics switching, upper/lower limit, 16-step 
speeds, starting frequency adjustment, jogging operation, carrier frequency 
adjustment, PID control, frequency jump, analog gain/bias adjustment, S shape 
acceleration/deceleration, electronic thermal characteristics, level 
adjustment, restart function, torque boost function, fault monitor, soft lock 
function, frequency conversion display, USP function, motor 2 control function, 
UP/DWN, overcurrent control function, etc.
Operating 
environ- 
ment
Ambient operating 
temperature
-10 to 50 °C (However, derating is required).
Ambient storage 
temperature
-20 °C to 65 °C
Ambient operating 
humidity
20% to 90% RH (with no condensation)
Vibration resistance 5.9 m/s2 (0.6G), 10 to 55 Hz
Application 
environment
At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust)
Options EtherCAT 
Communication Unit
3G3AX-MX2-ECT
CompoNet 
Communication Unit
3G3AX-MX2-CRT-E
DeviceNet 
Communication Unit
3G3AX-MX2-DRT-E
Other option DC reactor, AC reactor, radio noise filter, input noise filter, output noise filter, 
regenerative braking unit, Braking Resistor, etc.
Interna- 
tional 
standard
EC di- 
rective
EMC directive EN61800-3: 2004
Low voltage 
directive
EN61800-5-1: 2007
Machinery 
directives
IEC 60204-1 Stop Category 0, EN IEC 61800-5-2 (STO), EN ISO 13849-1: 2008 
(PLd)
UL/cUL UL508C